Check whether a fire alarm panel's standby batteries are big enough, using the minimum capacity formula from BS 5839-1:2025 Annex E.
Based on BS 5839-1:2025 Annex E · Last reviewed October 2026
BS 5839-1:2025 Annex E gives the minimum battery capacity needed to run the system on standby for the required period, then in full alarm for 30 minutes, with allowances for battery ageing and for the lower efficiency of a battery at high discharge rates:
Cmin = 1.25 × ((T1 × I1) + D × (I2 × T2))
The battery passes when its rated capacity is at least Cmin. If it fails, the calculator suggests the next common battery size above Cmin.
The calculator offers the two most common periods, 24 and 72 hours. For any other period, choosing the next longer option gives a safe (larger) answer.
Always-on network equipment — IP communicators, dual-path signalling units and remote access modules — draws current continuously, so include it in the standby figure. Typical draw is 0.02–0.08 A; check the manufacturer's specification for the unit fitted.